Variable Speed Drive

A Variable Frequency Drive (VFD) is a type of engine controller that drives a power motor by varying the frequency and voltage supplied to the electric motor. Other names for a VFD are adjustable speed drive, adjustable velocity drive, adjustable frequency drive, AC drive, microdrive, and inverter.
Frequency (or hertz) is directly linked to the motor’s quickness (RPMs). In other words, the quicker the frequency, the faster the RPMs move. If an application does not require a power motor to run at full velocity, the VFD can be used to ramp down the frequency and voltage to meet the requirements of the electrical motor’s load. As the application’s motor velocity requirements alter, the VFD can merely arrive or down the motor speed to meet the speed requirement.
The first stage of a Variable Frequency AC Drive, or VFD, may be the Converter. The converter is certainly made up of six diodes, which are similar to check valves used in plumbing systems. They enable current to stream in only one direction; the path shown by the arrow in the diode symbol. For instance, whenever A-stage voltage (voltage is similar to pressure in plumbing systems) is definitely more positive than B or C stage voltages, after that that diode will open up and allow current to flow. When B-phase turns into more positive than A-phase, then the B-phase diode will open and the A-phase diode will close. The same holds true for the 3 diodes on the adverse part of the bus. Hence, we get six current “pulses” as each diode opens and closes. This is known as a “six-pulse VFD”, which is the standard configuration for current Adjustable Frequency Drives.
Let us assume that the drive is operating on a 480V power program. The 480V rating is certainly “rms” or root-mean-squared. The peaks on a 480V system are 679V. As you can plainly see, the VFD dc bus has a dc voltage with an AC ripple. The voltage runs between approximately 580V and 680V.
We can eliminate the AC ripple on the DC bus by adding a capacitor. A capacitor operates in a similar style to a reservoir or accumulator in a plumbing system. This capacitor absorbs the ac ripple and provides a easy dc voltage. The AC ripple on the DC bus is typically significantly less than 3 Volts. Therefore, the voltage on the DC bus turns into “approximately” 650VDC. The real voltage depends on the voltage level of the AC range feeding the drive, the level of voltage unbalance on the energy system, the electric motor load, the impedance of the power system, and any reactors or harmonic filters on the drive.
The diode bridge converter that converts AC-to-DC, may also be just referred to as a converter. The converter that converts the dc back again to ac is also a converter, but to distinguish it from the diode converter, it is generally known as an “inverter”. It is becoming common in the market to refer to any DC-to-AC converter as an inverter.
When we close one of the top switches in the inverter, that phase of the electric motor is linked to the positive dc bus and the voltage upon that stage becomes positive. Whenever we close one of the bottom switches in the converter, that phase is linked to the unfavorable dc bus and becomes negative. Thus, we can make any stage on the electric motor become positive or detrimental at will and will thus generate any frequency that we want. So, we can make any phase be positive, negative, or zero.
If you have a credit card applicatoin that does not have to be run at full swiftness, then you can decrease energy costs by controlling the motor with a adjustable frequency drive, which is among the advantages of Variable Frequency Drives. VFDs enable you to match the rate of the motor-driven apparatus to the load requirement. There is no other approach to AC electric motor control which allows you to accomplish this.
By operating your motors at most efficient speed for the application, fewer errors will occur, and therefore, production levels will increase, which earns your firm higher revenues. On conveyors and belts you eliminate jerks on start-up enabling high through put.
Electric motor systems are responsible for more than 65% of the power consumption in industry today. Optimizing electric motor control systems by setting up or upgrading to VFDs can reduce energy consumption in your facility by as much as 70%. Additionally, the use of VFDs improves item quality, and reduces production costs. Combining energy efficiency taxes incentives, and utility rebates, returns on investment for VFD installations can be as little as six months.